Skip to main content
Open search engine
Search
Close search engine Clear Search
Products in the cart: 0. See details

Your cart is empty

English / €

Addressable water leak sensor WLS-MB

with VAT without VAT
Price €136.59
incl. 23% VAT

Shipping costs are not included in the price.

Planning a longer-term partnership?
Get in touch with us — we offer individual pricing terms for business partners.
pcs.
Availability:
in stock
Shipping time: 24 hours

Protect your facility against water leaks

with the WLS-MB water leak detection sensor

WLD-24P detector installation

Why choose WLS-MB?

The WLS-MB water leak detection sensor is a reliable device designed to protect rooms and equipment against the effects of water leakage. It is available in versions with sensing cable lengths up to 50 m. The presence of water is indicated via a two-wire communication bus compliant with the alarm-profile M-Bus protocol, as well as by LED indication. Using the communication bus allows flexible topology and significantly reduces the amount of cabling required. The device also performs automatic sensing cable continuity monitoring.

Key benefits

Pinpoint risk faster

The device serial number also serves as its M-Bus network address, enabling fast and unambiguous identification.

Reduce diagnostic time

The device reports both water leak alarms and sensing cable faults, helping maintain reliable system operation.

Install with ease

Bus power and flexible topology help reduce installation time and cabling costs.

Choose the right sensing cable length

Available lengths from 30 cm to 50 m make it easy to match the sensor to the application — from server rooms to storage areas.

Automatic calibration and continuity check

The device automatically checks sensing cable continuity and adjusts measurement sensitivity, reducing service effort and minimizing the risk of error.

Durable construction

The sensing cable is made of corrosion-resistant, non-water-absorbing materials, allowing fast drying and a quick return to standby condition.

 

Comparison of water leak detection solutions

Feature WLS-TR WLS-MB WLD-24P + WLSxx
Available Yes Yes No
Sensor cable connection Integrated Integrated Separate
Alarm signal Transistor output M-Bus Relay
Power supply 24 V DC From the M-Bus 24 V AC/DC
Audible indication No No Yes
LED indication Yes Yes Yes
Manual alarm reset No No Yes
Sensing cable continuity monitoring Yes Yes No
Device status monitoring No Yes Yes
Configuration / update via the bus No Yes No

Sensor connection

The WLS-MB sensor communicates using the alarm-profile M-Bus protocol compliant with EN 13757-3 Annex D. The system requires the BLC-MBUS-ALM communication gateway, which acts as the M-Bus master. It powers the sensors and initiates communication. System status is mapped to standard BACnet objects.