WLD-24P
Water Leak Detector
DESCRIPTION
DIMENSIONS
CONNECTION
CONFIGURATION
SPECIFICATION
Power Supply | |
Voltage | AC/DC 24 V (12-30 V) |
Power Consumption | 1,3 VA / 1,0 W |
Alarm Relay | |
Contact | SPDT |
Rated Voltage | AC 250 V |
DC 30 V | |
Rated Current | 10 A |
Rated Load AC1 | 2500 VA |
Rated Load AC15 | 500 VA |
Motor Rating AC 230 V | 370 W |
Min. Switching Load | 500 mW |
Sound Alarm | |
Frequency | 2400 Hz |
Sound Level | 85 dB at 10 cm |
LED Indicator | |
Ready | continuous green |
Water Leak Alarm | blinking red |
Waiting for Reset | continuous red |
Configuration Options | |
Manual Reset | dipswitch 1 - On/Off |
Sound Alarm | dipswitch 2 - On/Off |
Sensitivity | dipswitch 4,5,6 - 5..40 uS |
Housing | |
Material | self-extinguishing PC/ABS |
Protection IEC605529 | front panel IP40 |
body with connectors IP20 | |
Dimensions DIN43880 | 2 slots of 18 mm |
Dimensions HxWxD | 91x36x62 mm |
Weight | 88 g |
Terminal Blocks | |
Type | screw |
Pluggable | no |
Cable Size | 0,14 - 2,5 mm2 |
Torque | 0,57 Nm |
Mounting | |
Distribution Boards | DIN43880 |
Fixing | on TH35 rail (IEC60715) |
Operation Ambient | |
Temperature | 0 - 50°C |
Relative Humidity | 10-90% (non condensing) |